Common
|
Standard Features
|
1ø to 3ø programmable (TW 5250 only) WaveForm trigger output (1 M Load Drive) SYNC OUT
|
Programmed Settings
|
The Sync out selections are: Even Cycle A phase (on) None (off) When change in programmed parameters occur (event) External Summing Node 0 to 5 Vrms provides 0 to 100% output
|
Interface
|
IEEE-488.2 interface and RS-232
|
Protocol
|
SCPI protocol
|
Certifications
|
CE marked and FCC compliant
|
Calibration Interval
|
1 year
|
Input
|
Voltage Ranges
|
Factory configured 187 to 264 Vrms, 3ø L-L (3 wire). A chassis ground is also required.
|
Power Factor
|
0.6 (0.99 with input PFC option, 0.35 for European rectifier input)
|
Frequency Range
|
47 to 63 Hz
|
Efficiency
|
70% min, at full load
|
Ride Through
|
3 ms, min for rectifier input; 10 ms, min, with PFC option
|
Output
|
Power
|
1750 VA, 3500 VA or 5250 VA
|
Phase
|
1750 VA, 1 phase; 3500 VA, 1 or 2 phase; 5250 VA, 1, 2 or 3 phase
|
AC Output Voltage
|
0 to 156 Vrms L-N low range 0 to 312 Vrms L-N high range
|
DC Output Voltage
|
0 to 207V low range 0 to 414V high range
|
Current Per Phase
|
13A to 135V in 156V range; 6.5A to 270V in 312V range (per 1750 VA module); 16A to 115V in low range; 8A to 230V in high range (per 1850Va module)
|
Power Factor of Load
|
0 lagging to 0 leading
|
Crest Factor
|
4.0 (peak output current to rms output current)
|
Frequency Range
|
45 Hz to 500 Hz
|
Max Total Harmonic Distortion
|
0.3% max (Full Linear Load or No Load)
|
AC Noise Level
|
60 dB rms below full output voltage
|
Amplitude Stability With Remote Sense
|
±0.1% of full scale over 24 hours at constant line, load and temperature
|
Line Regulation
|
0.05% of full scale for a ± 10% change in line voltages
|
Load Regulation
|
0.15% of full scale
|
Voltage Accuracy
|
± 0.1% of full scale
|
Voltage Resolution
|
0.03% of full scale
|
Frequency Resolution
|
0.1 Hz
|
Phase Accuracy
|
Phase-to-Phase Balanced Linear Resistive Load: ±1°
|
Phase Angle Resolution
|
0.1°
|
Remote Output Voltage Sense
|
5 Vrms total lead drop, max
|
Environmental
|
Operating Temperature
|
0°C to 45°C (32°F to 113°F)
|
Storage Temperature
|
-40°C to 70°C (-40°F to 158°F)
|
Cooling
|
Air is drawn in primarily from the front, but also from the top, bottom, and sides and exhausted through the rear.
|
Humidity (Non-condensing)
|
0 to 85%, 31°C (88°F); derate to 50% at 40°C (104°F)
|
Altitude
|
Operating 6,500 ft. Non-operating 40,000 ft
|
Physical
|
Dimensions
|
Width: 19"" (483 mm) Height: 8.75"" (222 mm) Depth: 24.1"" (613 mm)
|
Weight
|
TW 1750 - 60 lbs. (27.3 kg), TW 3500 - 83 lbs. (37.7 kg), TW 5250 - 108 lbs. (49 kg)
|
Shipping Weight - US
|
TW 1750 - 130 lbs. (59 kg), TW 3500 -153 lbs. (69.5 kg), TW 5250 - 178 lbs. (80.9 kg)
|
Measurement Accuracy All at 25° ± 5°C
|
Power
|
2.5% of full scale
|
Voltage
|
0.3% of full scale + 0.2% of reading
|
Shipping Weight
|
12.7 lbs. (5.8 kg)
|
Current
|
0.3% of full scale + 0.5% of reading
|
Apparent Power
|
2.5% for output > 200 VA
|
Frequency
|
0.25%
|
Phase
|
0.5°
|
Protection and Safety
|
Overvoltage Shutdown
|
Programmable for 20V to 255V peak, 156V range; 40V to 510V peak, 312V range
|
Programmable Current Limit Shutdown
|
Settable to 1% of range (0.5A to 13A for 156V range; 0.5A to 6.5A for 312V range)
|
Programmable Current Limit with Timed Shutdown
|
Settable to 1% for range; the timeout is settable from 10 ms to 10s
|
Programmable Constant Current
|
Settable to 1% of range (0.5A to 13A for 156V range; 0.5A to 6.5A for 312V range). For all current accuracies, add ± 1.5%/ kHz above 500 Hz. For paralleled amplifiers, add ± 1%.
|
Over temperature Shutdown
|
Automatic, not programmable
|