Common |
Remote Sense |
Terminals are provided to sense output voltage at point of load. Maximum line drop 5% of rated voltage per line for 40-100V models, line drop 1V of rated voltage per line for 10-20V models, 1.5V for 30V models, 2% of rated voltage per line for models 160V and greater. (Greater line drop is allowed, but output regulation specifications no longer apply). |
Parallel Operation |
Up to 5 units may be paralleled for additional current within the power supply single-unit specifications, with exception of the DC output current set accuracy. Additional paralleled SG units will add 0.3% inaccuracy per unit. To parallel more than 5 units, contact factory. |
Series Operation |
Up to 2 units (see Output Float Voltage) |
Input |
Nominal Voltage
3 phase, 3 wire + ground |
208/220 VAC (operating range 187 - 242 VAC)
380/400 VAC (operating range 342 - 440 VAC)
440/480 VAC (operating range 396 - 528 VAC) |
Frequency |
47 - 63Hz , 400Hz ( 400Hz @ 208VAC, for 6U units is optional modification and does not carry CE, UL or CSA markings ) |
Power Factor |
>0.9 typical for 10V - 30V, 50V, 1000V and other models with optional “PF“ modification.
>0.75 typical for 208/220 VAC input
(40V, 60V - 800V models, 0.9 available with modification “PF“)
>0.72 typical for 380/480 VAC input
(40V, 60V - 800V models, 0.9 available with modification “PF“)
>0.69 typical for 440/480 VAC input
(40V, 60V - 800V models, 0.9 available with modification “PF“) |
Protection |
½ cycle ride-though , typical, on all three phases, 3 cycle ride through on single phase; missing phase shutdown ( 800V model 6.4 msec on all 3 phases ) |
SORENSEN SG Series
|
Power
Unit Weight: |
5kW
52 lbs.
|
10kW
66 lbs.
|
15kW
80 lbs.
|
20kW
132 lbs.
|
25kW
146 lbs.
|
30kW
160 lbs.
|
Shipping Weight |
62 lbs
|
76 lbs.
|
115 lbs.
|
167 lbs.
|
181 lbs.
|
195 lbs.
|
Dimensions: L/W/H |
26.4"" x 19"" x 5.25""
|
26.4"" x 19"" x 5.25""
|
26.4"" x 19 x 5.25""
|
25"" x 19"" x 10.5""
|
25"" x 19"" x 10.5""
|
25"" x 19"" x 10.5""
|
(40V and above)
|
Voltage-Current Combinations:
(rounded to whole A) |
40X125
|
40X250
|
40X375
|
**
|
**
|
**
|
50X100
|
50X200
|
50X300
|
**
|
**
|
**
|
60X83*
|
60X167*
|
60X250*
|
60-333*
|
60-417*
|
60-500*
|
80X63
|
80X125
|
80X188
|
80-250
|
80-313
|
80-375
|
100X50*
|
100X100*
|
100X150*
|
100-200*
|
100-250*
|
100-300*
|
160X31*
|
160X63*
|
160X94*
|
160-125*
|
160-156*
|
160-188*
|
200X25
|
200X50
|
200X75
|
200-100
|
200-125
|
200-150
|
250X20
|
250X40
|
250X60
|
250-80
|
250-100
|
250-120
|
330X15
|
330X30
|
330X45
|
330-61
|
330-76
|
330-91
|
400X12
|
400X25
|
400X38
|
400-50
|
400-63
|
400-75
|
600X8
|
600X17
|
600X25
|
600-33
|
600-42
|
600-50
|
800X6
|
800X13
|
800X19
|
**
|
**
|
**
|
SORENSEN SG Series
|
Power
Unit Weight: |
4kW
65 lbs.
|
5kW
65 lbs.
|
8kW
85 lbs.
|
10kW
85 lbs.
|
12kW
110 lbs.
|
15kW
110 lbs.
|
Shipping Weight |
85 lbs
|
85 lbs
|
105 lbs.
|
105 lbs.
|
130 lbs.
|
130 lbs.
|
Dimensions: L/W/H |
26.5"" x 19"" x 5.25""
|
26.5"" x 19"" x 5.25""
|
26.5"" x 19"" x 5.25""
|
26.5"" x 19"" x 5.25""
|
26.5"" x 19"" x 5.25""
|
26.5"" x 19"" x 5.25""
|
(30V and below)
|
Voltage-Current Combinations: |
10X400
|
|
10X800
|
|
10X1k2 (1200)
|
|
15X267
|
|
15X534
|
|
15X801
|
|
|
20X250
|
|
20X500
|
|
20X750
|
|
30X167
|
|
30X334
|
|
30X501
|
Environmental |
Operating Temperature |
0 to 50º C |
Storage Temperature |
-25º C to 65º C |
Humidity Range |
Relative humidity up to 95% non-condensing, 0º C - 50º C |
Altitude |
Operating full power available up to 5,000 ft. (~1,500 m), derate 10% of full power for every 1,000 feet higher; non-operating to 40,000 ft. (~12,000 m) |
Cooling |
Front and side air inlet, rear exhaust. Temperature controlled, variable speed fans. Units may be stacked without spacing. |
Regulatory |
Certified to UL/CSA 61010 and IEC/EN 61010-1 by a NRTL, CE Compliant, Semi-F47 Compliant.
LVD Categories: Installation Category II: Pollution Degree 2; Class II Equipment: for Indoor Use Only, back panel not user accessible
(see user manual for installation instructions)
EMC Directive, EN 61326:1998 |
Front Panel Dust Filter |
30 PPI (Pores Per Inch) - must ensure adequate airflow and / or derate max. temperature.
3U unit only. |
Output |
Ripple & Noise (Voltage Mode, Typical) |
See Output: Voltage & Current Ranges Chart above. Ripple and noise specified at full load, nominal AC input. Noise measured with 6ft. cable, 1μf at load |
Ripple (Current Mode) |
<+/- 0.04% of full scale rms current |
DC Voltage Slew Rate (40-800V) |
‰ˆ< 100 ms 5-95% of full scale typical - resistive load (Contact factory for model specific slew rates) |
Output Voltage Rise Time
(10-30V) |
Rise Time, ms, MAX
|
Condition
|
10
|
Measured from 10% to 90% of the output voltage change - resistive load, typical
|
Output Voltage Fall Time
(10-30V) |
Fall Time, MS MAX
|
Condition
|
No Load 1
50
|
100% CC Load 10
|
100% CR Load 10
|
Measured from 90% to 10% of the output voltage change. - resistive load, typical
|
Output Current Rise Time
(10-30V) |
Rise Time, ms, MAX
|
Condition
|
20
|
Measured from 10% to 90% of the output current change - resistive load, typical
|
Output Current Fall Time
(10-30V) |
Rise Time, ms, MAX
|
Condition
|
10
|
Measured from 90% to 10% of the output current change - resistive load, typical
|
DC Current Slew Rate |
45A / ms typical - resistive load |
Line Regulation (with sense wires used) |
(±10% of nominal AC input, constant load)
Voltage Mode: +/- 0.01% of full scale (40-800V)
Current Mode: +/- 0.05% of full scale (40-800V)
Voltage Mode and Current Mode: +/- 0.05% of full scale (10-30V) |
Load Regulation (with sense wires used) |
(no load to full load, nominal AC input)
Voltage Mode: +/- 0.02% of full scale (40-800V)
Current Mode: +/- 0.1% of full scale
Voltage Mode: +/- 0.05% of full scale (10-30V) |
Load Transient Response |
Recovers within 1ms to +/-0.75% of full-scale of steadystate output for a 50% to 100% or 100% to 50% load change |
Efficiency |
87% typical at nominal line and max load |
Stability |
±0.05% of set point after 30 minute warm-up and over 8 hours at fixed line, load and temperature, typical |
Temperature Coefficient |
0.02%/ C of maximum output voltage rating for voltage set point, typical
0.03%/ C of maximum output current rating for current set point, typical |
Output Float Voltage |
Negative terminal within +/- 300 V of chassis potential.
(We recommend the use of optional isolated analog Interface (IAI).) Supplies in ""series"" should be the same output voltage/current, in not system current is limited to lower of the two supplies. |