Product Type
|
The Multi-Zone Gas Leak Monitor is a multiple area monitoring system for low level continuous monitoring of refrigerant gases used in most commercial systems including; CFC, HCFC, HFC and Ammonia. System design supports compliance to gas monitoring requirements of ANSI/BSR ASHRAE 15-1994.
|
Gas Library
|
HGM-MZ:
|
CFC: R11, R12, R113, R114, R502, HFP HFC: R404A (HP62), R407A, R407C (AC9000), R134A, R410A (AZ20), HFC: R507 (AZ50) HCFC: R21, R22, R23, R123, R124, R227, R500, R503, R401A (MP39), R402A (HP80), R402 (HP81), R408A, R409A, R508B (SUVA95), R236FA, R125, R245FA, R422A, R422D, R427A Halon: H1301, H2402, H1211 Other: FA188, FC72, N1230, HFO1234YF, R424A, R426A, R427A, R438A
|
AGM-MZ:
|
Ammonia (NH3), R717
|
CO2-MZ:
|
Carbon Dioxide (CO2), R744
|
Sensitivity
|
All gases 1 ppm (R11 ± 10 ppm ± 15% of reading 0-1000 ppm)
|
Measuring Range
|
HGM-MZ:
|
All gases 0 to 10,000 ppm
|
AGM-MZ:
|
Ammonia 25 to 10,000 ppm
|
CO2-MZ:
|
Carbon Dioxide 0 to 8,000 ppm
|
Accuracy
|
HGM-MZ:
|
±1 ppm ±10% of reading from 0-1,000 ppm (R11, R22, R13: ±10 ppm ±15% of reading 0-1,000 ppm)
|
AGM-MZ:
|
±10 ppm ±10% of reading from 0-1,000 ppm
|
CO2-MZ:
|
±5 ppm ±5% of reading from 0-1,000 ppm, ±10% of reading from 1,000 to 4,000 ppm, ±15% of reading 4,000 to 8,000 ppm
|
Front Panel
|
3 indicator lights
Green = Monitor is powered on. LED glows during normal operation; flashes when unit is in warm-up mode
Red = Alarm. LED flashes when any point has exceeded the alarm setting
Yellow = Fault. LED flashes when there is a system fault
|
Size & Weight
|
12.23"" H x 13.7"" W x 4.96"" D / 15lbs.
|
Temperature Drift
|
HGM-MZ:
|
±0.8% (R134A) of reading per Degrees C between purge cycles
|
AGM-MZ:
|
1.5 ppm per Degrees C between purge cycles
|
CO2-MZ:
|
Less than 1 ppm per Degrees C between purge cycles
|
Coverage
|
4 point standard, expandable to 16 points in 4 point increments
|
Detector Type
|
Infrared Non-Dispersive
|
Sampling Mode
|
Automatic or Manual (hold)
|
Re-Zero
|
Auto or on Zone Change
|
Response Time
|
5 to 120 seconds — depending on air line length and number of zones
|
System Noise
|
Less than 40dB(A) @ 10 feet (3m)
|
Monitoring Distance
|
1,200 ft. maximum for combined length of sample + exhaust tubing (each zone)
|
Conditional System
|
Dual optional 4-20mAdc isolated outputs. Channel 1 = zone area, Channel 2 = PPM
|
Alarms
|
Four SPDT alarm contacts are provided (rated 5 Amps at 250 volts). Three assigned to PPM level alarms, one assigned to system faults
|
Communications
|
Full two-way communications with proper remote display module or building management system via RS485 MODBUS-RTU serial interface. RS-232C communications port standard
|
Power Safety Mode
|
Fully automatic system reset. All programmed parameters retained
|
Operating Temp.
|
32 to 122 °F (0 to 50 °C)
|
Ambient Humidity
|
5% to 90% RH (non-condensing)
|
AC Power
|
100 to 240 VAC, 50/60 Hz, 20 W
|
Certification
|
UL 61010-1, Can/CSA 22.2 No. 61010-1 & CE Mark
|
Warranty
|
2 years from date of shipment
|
Altitude Limit
|
6,562 ft (2,00 m)
|