Logger
|
Power supply
|
Functional Range:
|
88 V to 660 V absolute, 50 Hz / 60 Hz 100 V to 350 V dc Internal fuse: 630 mA T
|
Power consumption:
|
5 Watts
|
Ride through:
|
Fluke 1745: Internal battery for typ. > 5 hours ride through with intelligent power management Fluke 1743/44: 3 sec Capacitor
|
Fuse:
|
Power supply fuse can be replaced in service facility only. Supply can be connected in parallel to measuring inputs (up to 660 V)
|
|
Display, indicators
|
|
LEDs for status and voltage levels Fluke 1745: LC-display with backlight for voltage, current, active power, phase sequence.
|
|
Memory
|
|
Capacity 8 MB Flash-EPROM
|
Intervals:
|
A function > 12000 intervals for > 85 days with 10 min intervals P function > 30000 intervals for > 212 days with 10 min intervals
|
Events:
|
> 13000
|
Memory model:
|
linear, circular
|
|
Interface
|
|
RS 232, 9600...115 000 Baud, automatic Baud rate selection, 3-wire communication
|
|
Dimensions
|
Fluke 1745:
|
282 mm x 216 mm x 74 mm (115in x 88in x 33in)
|
Fluke 1743/1744:
|
170 mm x 125 mm x 55 mm (69in x 51in x 22in)
|
|
Weight
|
Fluke 1745:
|
approx. 3 kg
|
Fluke 1744/1743:
|
approx. 2 kg
|
|
Measurement
|
A/D converter:
|
16 bit, sample rate: 10.24 kHz
|
Anti-aliasing filter:
|
FIR-Filter, fc =4.9 kHz
|
Frequency response:
|
Uncertainty < 1 % of Vm for 40 Hz to 2500 Hz
|
Interval length:
|
1, 3, 5, 10, 30 s, 1, 5, 10, 15, 60 minutes
|
Averaging time for Min/max values:
|
½, 1 mains period, 200 ms,1 , 3 , 5 s
|
Time base:
|
Resolution: 10 ms (at 50 Hz), deviation: 2s/day at 23 °C; 74 °F ± 2 K
|
|