| Logger | 
| Power supply | 
| Functional Range: |  88 V to 660 V absolute, 50 Hz / 60 Hz100 V to 350 V dc Internal fuse: 630 mA T
 |  
| Power consumption: |  5 Watts |  
| Ride through: |  Fluke 1745: Internal battery for typ. > 5 hours ride through with intelligent power managementFluke 1743/44: 3 sec Capacitor
 |  
| Fuse: |  Power supply fuse can be replaced in service facility only. Supply can be connected in parallel to measuring inputs (up to 660 V) |  | 
| Display, indicators | 
|  |  LEDs for status and voltage levelsFluke 1745: LC-display with backlight for voltage, current, active power, phase sequence.
 |  | 
| Memory | 
|  |  Capacity 8 MB Flash-EPROM |  
| Intervals: |  A function > 12000 intervals for > 85 days with 10 min intervalsP function > 30000 intervals for > 212 days with 10 min intervals
 |  
| Events: |  > 13000 |  
| Memory model: |  linear, circular |  | 
| Interface | 
|  |  RS 232, 9600...115 000 Baud, automatic Baud rate selection, 3-wire communication |  | 
| Dimensions | 
| Fluke 1745: |  282 mm x 216 mm x 74 mm (115in x 88in x 33in) |  
| Fluke 1743/1744: |  170 mm x 125 mm x 55 mm (69in x 51in x 22in) |  | 
| Weight | 
| Fluke 1745: |  approx. 3 kg |  
| Fluke 1744/1743: |  approx. 2 kg |  | 
| Measurement | 
| A/D converter: |  16 bit, sample rate: 10.24 kHz |  
| Anti-aliasing filter: |  FIR-Filter, fc =4.9 kHz |  
| Frequency response: |  Uncertainty < 1 % of Vm for 40 Hz to 2500 Hz |  
| Interval length: |  1, 3, 5, 10, 30 s, 1, 5, 10, 15, 60 minutes |  
| Averaging time for Min/max values: |  ½, 1 mains period, 200 ms,1 , 3 , 5 s |  
| Time base: |  Resolution: 10 ms (at 50 Hz), deviation: 2s/day at 23 °C; 74 °F ± 2 K |  |