Inputs
|
Number:
|
4 voltage and current (3 phases + neutral)
|
Maximum voltage:
|
1000 Vrms (6 kV peak)
|
Maximum sampling speed:
|
200 kS/s on each channel simultaneously
|
|
Volt/Amps/Hertz
|
Vrms (AC + DC)
|
|
Measurement range:
|
1 ... 1000 V
|
Accuracy:
|
0.1% of Vnom
|
|
|
Vpeak
|
|
Measurement range:
|
1 ... 1400 V
|
Accuracy:
|
5% of Vnom
|
|
|
Crest factor, voltage
|
|
Measurement range:
|
1.0 ... > 2.8
|
Accuracy:
|
±5%
|
|
|
Arms (AC + DC)
|
|
Measurement range:
|
0 ... 20 kA
|
Accuracy:
|
±0.5% ± 5 counts
|
|
|
Apeak
|
|
Measurement range:
|
1.4x rms value
|
Accuracy:
|
5%
|
|
|
Crest factor, A
|
|
Measurement range:
|
1 ... 10
|
Accuracy:
|
±5%
|
|
|
Hz 50 Hz nominal
|
|
Measurement range:
|
40 ... 70 Hz
|
Accuracy:
|
±0.01 Hz
|
|
Dips and swells
|
Vrms (AC+DC) ²
|
|
Measurement range:
|
0.0% … 100% of Vnom
|
Accuracy:
|
±0.2% of nominal voltage
|
|
|
Arms (AC+DC) ²
|
|
Measurement range:
|
0 ... 20 kA'
|
Accuracy:
|
±1% ± 5 counts
|
|
Harmonics
|
Harmonic (interharmonic) (n)
|
|
Measurement range:
|
DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7
|
|
|
Vrms
|
|
Measurement range:
|
0.0 … 1000 V
|
Accuracy:
|
±0.05% of nominal voltage
|
|
|
Arms
|
|
Measurement range:
|
0.0 … 4000 mV x clamp scaling
|
Accuracy:
|
±5% ± 5 counts
|
|
|
Watts
|
|
Measurement range:
|
Depends on clamp scaling and voltage
|
Accuracy:
|
±5% ± n x 2% or reading, ± 10 counts
|
|
|
DC voltage
|
|
Measurement range:
|
0.0 … 1000 V
|
Accuracy:
|
±0.2% of nominal voltage
|
|
|
THD
|
|
Measurement range:
|
0.0 … 100.0%
|
Accuracy:
|
±2.5% V and A (± 5% Watt)
|
|
|
Hz
|
|
Measurement range:
|
0 … 3500 Hz
|
Accuracy:
|
± 1 Hz
|
|
|
Phase angle
|
|
Measurement range:
|
-360º ... +360º
|
Accuracy:
|
± n × 1.5º
|
|
Power and energy
|
Watt, VA, VAR
|
|
Measurement range:
|
1.0 … 20.00 MVA¹
|
Accuracy:
|
±1% ± counts
|
|
|
kWh, kVAh, kVARh
|
|
Measurement range:
|
00.00 …200.0 GVAh¹
|
Accuracy:
|
± 1.5% ± 10 counts
|
|
|
Power Factor/ Cos Ф / DPF
|
|
Measurement range:
|
0…1
|
Accuracy:
|
± 0.03
|
|
Unbalance
|
Volts
|
|
Measurement range:
|
0.0 … 5.0%
|
Accuracy:
|
±0.5%
|
|
|
Current
|
|
Measurement range:
|
0.0 … 20%
|
Accuracy:
|
± 1%
|
|
Logging
|
Sampling:
|
5 readings/sec continuous sampling per channel
|
Readings:
|
User selectable up to 100 readings on 3 phases and neutral simultaneously
|
Averaging:
|
2hr down to 0.5s user selectable
|
Memory:
|
User selectable up to 7MB of shared memory
|
Recording time:
|
User selectable, depends on selected number of readings
|
Zoom:
|
Yes
|
|
Autotrend recording
|
Sampling:
|
5 readings/sec continuous sampling per channel
|
Memory:
|
1800 min, max and avg points for each reading
|
Recording time:
|
Up to 450 days
|
Zoom:
|
Up to 12x horizontal zoom
|
|
Memory
|
Screens & data:
|
50, shared memory divided between logging, screens and data sets
|
|
Notes
|
¹
|
Depending on clamp scaling
|
²
|
Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle
|
|