| Inputs | 
| Number: |  4 voltage and current (3 phases + neutral) |  
| Maximum voltage: |  1000 Vrms (6 kV peak) |  
| Maximum sampling speed: |  200 kS/s on each channel simultaneously |  | 
| Volt/Amps/Hertz | 
| Vrms (AC + DC) |   |  
| Measurement range: |  1 ... 1000 V |  
| Accuracy: |  0.1% of Vnom |  
|  |   |  
| Vpeak |   |  
| Measurement range: |  1 ... 1400 V |  
| Accuracy: |  5% of Vnom |  
|  |   |  
| Crest factor, voltage |   |  
| Measurement range: |  1.0 ... > 2.8 |  
| Accuracy: |  ±5% |  
|  |   |  
| Arms (AC + DC) |   |  
| Measurement range: |  0 ... 20 kA |  
| Accuracy: |  ±0.5% ± 5 counts |  
|  |   |  
| Apeak |   |  
| Measurement range: |  1.4x rms value |  
| Accuracy: |  5% |  
|  |   |  
| Crest factor, A |   |  
| Measurement range: |  1 ... 10 |  
| Accuracy: |  ±5% |  
|  |   |  
| Hz 50 Hz nominal |   |  
| Measurement range: |  40 ... 70 Hz |  
| Accuracy: |  ±0.01 Hz |  | 
| Dips and swells | 
| Vrms (AC+DC) ² |   |  
| Measurement range: |  0.0% … 100% of Vnom |  
| Accuracy: |  ±0.2% of nominal voltage |  
|  |   |  
| Arms (AC+DC) ² |   |  
| Measurement range: |  0 ... 20 kA' |  
| Accuracy: |  ±1% ± 5 counts |  | 
| Harmonics | 
| Harmonic (interharmonic) (n) |   |  
| Measurement range: |  DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7 |  
|  |   |  
| Vrms |   |  
| Measurement range: |  0.0 … 1000 V |  
| Accuracy: |  ±0.05% of nominal voltage |  
|  |   |  
| Arms |   |  
| Measurement range: |  0.0 … 4000 mV x clamp scaling |  
| Accuracy: |  ±5% ± 5 counts |  
|  |   |  
| Watts |   |  
| Measurement range: |  Depends on clamp scaling and voltage |  
| Accuracy: |  ±5% ± n x 2% or reading, ± 10 counts |  
|  |   |  
| DC voltage |   |  
| Measurement range: |  0.0 … 1000 V |  
| Accuracy: |  ±0.2% of nominal voltage |  
|  |   |  
| THD |   |  
| Measurement range: |  0.0 … 100.0% |  
| Accuracy: |  ±2.5% V and A (± 5% Watt) |  
|  |   |  
| Hz |   |  
| Measurement range: |  0 … 3500 Hz |  
| Accuracy: |  ± 1 Hz |  
|  |   |  
| Phase angle |   |  
| Measurement range: |  -360º ... +360º |  
| Accuracy: |  ± n × 1.5º |  | 
| Power and energy | 
| Watt, VA, VAR |   |  
| Measurement range: |  1.0 … 20.00 MVA¹ |  
| Accuracy: |  ±1% ± counts |  
|  |   |  
| kWh, kVAh, kVARh |   |  
| Measurement range: |  00.00 …200.0 GVAh¹ |  
| Accuracy: |  ± 1.5% ± 10 counts |  
|  |   |  
| Power Factor/ Cos Ф / DPF |   |  
| Measurement range: |  0…1 |  
| Accuracy: |  ± 0.03 |  | 
| Unbalance | 
| Volts |   |  
| Measurement range: |  0.0 … 5.0% |  
| Accuracy: |  ±0.5% |  
|  |   |  
| Current |   |  
| Measurement range: |  0.0 … 20% |  
| Accuracy: |  ± 1% |  | 
| Logging | 
| Sampling: |  5 readings/sec continuous sampling per channel |  
| Readings: |  User selectable up to 100 readings on 3 phases and neutral simultaneously |  
| Averaging: |  2hr down to 0.5s user selectable |  
| Memory: |  User selectable up to 7MB of shared memory |  
| Recording time: |  User selectable, depends on selected number of readings |  
| Zoom: |  Yes |  | 
| Autotrend recording | 
| Sampling: |  5 readings/sec continuous sampling per channel |  
| Memory: |  1800 min, max and avg points for each reading |  
| Recording time: |  Up to 450 days |  
| Zoom: |  Up to 12x horizontal zoom |  | 
| Memory | 
| Screens & data: |  50, shared memory divided between logging, screens and data sets |  | 
| Notes | 
| ¹ |  Depending on clamp scaling |  
| ² |  Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle |  |