| OVERVIEW |
| CNV 508N4 MODELS |
| CNV 508N4 |
Coupling/decoupling network with 4A AC/DC per line |
| CNV 508N4.1 |
Coupling/decoupling network with 16A AC/DC per line |
| TECHNICAL DETAILS |
| CNV 508N4 |
| Nominal voltage |
250V AC/DC per line |
| Nominal current |
4A AC/DC per line |
| Max. test voltage |
3kV peak for 1MHz damped oscillatory wave
Source impedance 200 Ohm |
| CNV 508N4.1 |
| Nominal voltage |
250V AC/DC per line |
| Nominal current |
16A AC/DC per line |
| Max. test voltage |
3kV peak for 1MHz damped oscillatory wave |
| Source impedance |
200 Ohm |
| COMMON DATA (ALL MODELS) |
| OUTPUTS |
| DUT connectors |
4mm safety lab connectors |
| Indications |
LEDs to indicate selected coupling mode and lines to be tested |
| COUPLING MODES AS PER IEC 60255-22-1 |
| Differential Mode |
Line-to-line within one pair |
| Common Mode #1 |
Test between an individual port and all others (ports not coupled are floating) |
| Common Mode #2 |
Test between an individual port and all others (ports not coupled are connected to ground via capacitor) |
| GENERAL DATA |
| Dimensions |
19"" 3HU |
| Weight |
approx. 10kg (CNV 508N4)
approx. 25kg (CNV 508N4.1) |
| Supply voltage |
115/230V +10/-15%, 50/60Hz |
| Fuses |
2 x T2AT (230V) or 2 x T4AT (115V) |
| CN interface |
CN interface, 15pin SubD, for remote control by the OCS 500N6 |