| TECHNICAL DETAILS |
| VOLTAGE SURGE SIMULATOR, PULSE 1.2/50US |
| Voltage (o.c.) |
250V - 6,600V ±10% |
| Pulse front time |
1.2µs ± 30% |
| Pulse time to half value |
50µs ± 20% |
| Source impedance |
500Ohm |
| Energy |
0.5J ± 0.05J at each test level |
| Standard test levels |
0.55kV, 0.9kV, 3.0kV, 5.0kV, 6.6kV |
| Pulse forming |
As per IEC 60255-5 |
| Polarity |
Positive, negative or alternating |
| Event counter |
1 - 30,000 or endless |
| TRIGGER |
| Trigger of events |
Automatic, manual, external |
| CRO trigger |
5V trigger signal for oscilloscope |
| Synchronization |
0° - 360°, resolution 1° |
| Repetition rate |
6s - 999s, depending on the voltage |
| OUTPUT |
| Direct Via |
HV connector; Zi = 500Ohm
To connect externaltest boxes or devices |
| INTERFACE |
| Serial interface |
USB |
| Parallel interface |
IEEE 488, addresses 1 - 30 |
| GENERAL DATA |
| Dimensions |
19""/3HU |
| Weight |
approx. 18kg |
| Supply voltage |
115/230V +10/-15% |
| Fuses |
2xT2AT (230V) or 2xT4AT (115V) |